How to Use the Circuit Load Calculator
The calculator applies the 80% continuous load rule to show capacity, headroom, and breaker sizing for a circuit. It has three Calculation Modes: capacity, breaker, and wattage.
Open the Circuit Load Calculator
Before you start
- Collect the nameplate wattage (or amps) for every device on the circuit.
- Identify the circuit voltage (120 V and 220 V are built in; use Custom Voltage for anything else) and the breaker rating.
- Know whether the load will run 3 hours or longer, which makes it a continuous load.
Step by step
- Choose a Calculation Mode — Choose Capacity to compare a known breaker with your loads, Req. Breaker to find a minimum breaker rating, or Max Watts to find the peak and continuous wattage supported by a breaker.
- Set Voltage — Pick 120 or 220, or choose custom and type a Custom Voltage.
- Enter Breaker Amps — Set the breaker rating, for example 20 A. In Max Watts mode this and the voltage determine supported wattage; equipment loads are not needed.
- Add equipment loads — Enter each Equipment load in watts. Unfinished items are excluded from the running calculation for that circuit.
- Read the results — Capacity mode shows Theoretical Peak, Continuous Cap (80%), Current Draw, Headroom, and Status (Safe, Near limit, or Overloaded). Breaker mode shows Required Breaker and Recommended Breaker.
- Split across circuits — With several circuits, use Suggest split to balance loads, then accept it or choose Keep current plan.
- Save the numbers — Use Copy Results to paste the calculation into a text or show report. The plan is session only and clears when you leave or refresh.
Practical example: LED fixtures on a 20 A, 120 V circuit
A 20 A breaker at 120 V has a theoretical peak of 2,400 W and an 80% continuous cap of 1,920 W (16 A). Twelve LED wash fixtures at 125 W each total 1,500 W, a current draw of 12.5 A. The calculator reports 420 W of continuous headroom and a Safe status.
Safety and limitations
- Results are planning estimates. A qualified electrician must verify distribution, wiring, and code compliance.
- Nameplate watts do not include inrush current; motors, amplifiers, and some LED drivers can trip a breaker on power-up.
- Power factor and three-phase balancing are not modeled. Use the power tutorials and your master electrician for feeder work.